ELMBs in 2004
28 ELMBs are
connected to 3 CANbus lines with total length
of approx 400 m. ELMBs on CANbus lines 1 and 2 are of old type, while
ELMBs on CANbus line 3 are new type. To avoid cross-talk between different
detectors and their electronics, it was decided to have independent ELMBs for
each detectors or sub-system, whenever possible. The distribution of the
ELMBs over the experimental hall is optimized in order to have the shortest
wiring connections to sensors or monitoring points.
The monitoring is done using CANOpen OPC Server (CanOpc.exe), running on
na58pc014 PC(Windows 2000), installed in DCS room HNB423.
The configuration file for the OPC Server is located in the "OPC"
directory. A PVSS API manager "PVSS00opc -num 1", as a client,
connects to the OPCCanOpen Server. 3 ports of a Kvaser
PCI-CAN Q (4 ports) interface card are used (the card is in 4 indepent
ports configuration). The CANbus network consists of 3 CANbus branches, of
120 m, 210 m and 50m lenght. Due to their long length (>50 m), cable with
6 conducting wires with cross-section 0.5 mm2 for each is used
for CANbus1 and CANbus2 (multiconductor screened cable layer twisted, CERN
catalogue - 04.21.51.106.0), and cable with 8 conducting wires for
CANbus3.
A special transition board is used for the
ELMB connection to the network cable (see the scheme
here). The wires of
thick cable are ended by pins and screws on board contacts, which has printed
wiring between to Dsub 9 pin connector. The ELMB CANbus connector connects
to the transition board via a short(0,5 m) flat cable.
Each ELMB has its own local power supply and
there is only one central power supply for the CANbus. The system has full
optocoupling between nodes connected to CANbus line. The power supply for
the CANbus provides 12V and a current of 1.5-2 Amps, being located in the
DCS room, close to the na58pc014 PC. This powers the CANbus
receivers/transmitters, which are optically insulated from the ELMB internal
circuit. The ELMBs have their own local power supplies. As a rule, each ELMB
has a power supply for its analog part and another for the digital part.
In some cases one common power supply is used for both parts. The nominal
voltage of the power supplies is 12V. There are 2
types of power supplies used as local: Switching power supply
OMRON model S82K with 12V output, Imax=1.5A (mounted in a rail and with
protection cover); and Regulated Adapter type EP2, FRIWO with output
12V, Imax=0.5A.
Plugged to the ELMB's motherboard, 2 types
of adapters are used, depending of the input signals to the ELMB: High
performance Pt100 adapters, with Rc = 3.9 KOhm,
Rs = 100 Ohm (to be used with Pt4w temperature sensors); and
Differential attenuators with 1:100 divider
(100 KOhm/1 KOhm).
Different kinds of sensors are used,
depending on the parameters to be monitored. For temperature measurements
we use Pt100 sensors. The humidity
measurements are done using type HIH 3605A humidity
sensors. For pressure measurements, type
144S PCB Series is used. The magnetic field is measured with
UGN35 Hall probe.
In PVSS, there are several monitoring
parameters with associated alarm signals defined (so that an alarm will
be displayed if the read value goes out of a given min/max
threshold). The alarm causes changing the background colour of the alarm
text window, from green to red, orange or yellow. Also, the alarm signal
will be propagated to the top of the monitoring system hierarchy and cause
changing the colour of the ELMB_A button on the main COMPASS control
panel.
The monitoring parameters,
that can produce alarm signals are:
- T_W_DEP; T_W_RET.
These 2 parameters represent the temperatures of incoming and outgoing water
in the RICH electronics cooling system.
- SM1_M_F. Measurement of the stability of
SM1 magnetic field.
- B6_M_F. Measurement of the stability of
B6 magnetic field.
- PT_1_HSO; PT_2_DTF
; PT_3_SLT;
PT_4_MHG; PT_5_SCW;
PT_6_SFC; PT_7_NMR;
PT_8_SCL. These 8 parameters represent the temperatures of
different points in the Polarized Target platform.
- mW2_gas_alarm. This parameter
represents the status of gas system for mW2 detector.
- The following 16 parameters represent the temperatures of
different points on electronics readout boards of SILICON detectors:
SI02_T_u1;
SI01_T_u1;
SI02_T_u2;
SI01_T_u2;
SI02_T_v1;
SI01_T_v1 (sensor on SI03);
SI02_T_v2;
SI01_T_v2 (sensor on SI03);
SI02_T_y1;
SI01_T_y1;
SI02_T_y2;
SI01_T_y2;
SI02_T_x1;
SI01_T_x1 (sensor on SI03);
SI02_T_x2;
SI01_T_x2 (sensor on SI03).
ELMBs configuration
Jump to ELMB #:
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
- ELMB #1
CANbus line #1
ADC mode: unipolar; ADC range: 100 mV.
Place: HNB 425, DAQ room, temperature measurements.
Status: installed.
ADC channels |
Dp name |
Comments |
Status |
33 - 34 |
T_RB_1 |
Temperature inside Readout Buffer Rack 1 |
ON |
35 - 36 |
T_RB_2 |
Temperature inside Readout Buffer Rack 2 |
ON |
37 - 38 |
T_EB_1 |
Temperature inside Event Builder Rack 1 |
ON |
39 - 40 |
T_EB_2 |
Temperature inside Event Builder Rack 2 |
ON |
- ELMB #2
CANbus line #2
ADC mode: unipolar; ADC range: 100 mV.
Place: MW1 FE LV power supply rack, SM2 region, Jura side.
Status: installed.
Comments: Cable entering ELMB channels
0-15 labelled "ADC input 1"; to channels 16-31 labelled "ADC input 3";
to channels 32-47 labelled "ADC input 2". In PVSS the factors 0.6, 1.4
and 3.2 in the dp_fct are due to the VME crate itself: 10V means Vout=6V, etc.
ADC channels |
Dp name |
Comments |
Status |
1 |
mW1_C31_5Vp |
Crate #3, +5V, channel 1 |
ON |
2 |
mW1_C31_5Vn |
Crate #3, -5V, channel 1 |
ON |
3 |
mW1_C32_5Vp |
Crate #3, +5V, channel 2 |
ON |
4 |
mW1_C32_5Vn |
Crate #3, -5V, channel 2 |
ON |
5 |
mW1_C41_5Vp |
Crate #4, +5V, channel 1 |
ON |
6 |
mW1_C41_5Vn |
Crate #4, -5V, channel 1 |
ON |
7 |
mW1_C42_5Vp |
Crate #4, +5V, channel 2 |
ON |
8 |
mW1_C42_5Vn |
Crate #4, -5V, channel 2 |
ON |
9 |
mW1_C51_5Vp |
Crate #5, +5V, channel 1 |
ON |
10 |
mW1_C51_5Vn |
Crate #5, -5V, channel 1 |
ON |
11 |
mW1_C52_5Vp |
Crate #5, +5V, channel 2 |
ON |
12 |
mW1_C52_5Vn |
Crate #5, -5V, channel 2 |
ON |
17 |
mW1_V3_5Vp |
Crate VME #3, +5V voltage |
ON |
18 |
mW1_V3_5Ip |
Crate VME #3, +5V current |
ON |
19 |
mW1_V3_12Vp |
Crate VME #3, +12V voltage |
ON |
20 |
mW1_V3_12Ip |
Crate VME #3, +12V current |
ON |
21 |
mW1_V3_12Vn |
Crate VME #3, -12V voltage |
ON |
22 |
mW1_V3_12In |
Crate VME #3, -12V current |
ON |
23 |
mW1_V3_OVT |
Crate VME #3 PS Over-Temperature |
ON |
24 |
mW1_V3_OLD |
Crate VME #3 cards Over-Temperature |
ON |
33 |
mW1_V1_5Vp |
Crate VME #1, +5V voltage |
ON |
34 |
mW1_V1_5Ip |
Crate VME #1, +5V current |
ON |
35 |
mW1_V1_12Vp |
Crate VME #1, +12V voltage |
ON |
36 |
mW1_V1_12Ip |
Crate VME #1, +12V current |
ON |
37 |
mW1_V1_12Vn |
Crate VME #1, -12V voltage |
ON |
38 |
mW1_V1_12In |
Crate VME #1, -12V current |
ON |
39 |
mW1_V1_OVT |
Crate VME #1 PS Over-Temperature |
ON |
40 |
mW1_V1_OLD |
Crate VME #1 cards Over-Temperature |
ON |
41 |
mW1_V2_5Vp |
Crate VME #2, +5V voltage |
ON |
42 |
mW1_V2_5Ip |
Crate VME #2, +5V current |
ON |
43 |
mW1_V2_12Vp |
Crate VME #2, +12V voltage |
ON |
44 |
mW1_V2_12Ip |
Crate VME #2, +12V current |
ON |
45 |
mW1_V2_12Vn |
Crate VME #2, -12V voltage |
ON |
46 |
mW1_V2_12In |
Crate VME #2, -12V current |
ON |
47 |
mW1_V2_OVT |
Crate VME #2 PS Over-Temperature |
ON |
48 |
mW1_V2_OLD |
Crate VME #2 cards Over-Temperature |
ON |
63 - 64 |
pt4w_elmb2_T64 |
Pt4w temperature sensor, T11 |
ON |
- ELMB #3
CANbus line #1
ADC mode: unipolar; ADC range: 100 mV.
Place: BMS electronics room.
Status: installed.
ADC channels |
Dp name |
Comments |
Status |
1 |
bmse_lv_1p |
NIM crate #1, +6V |
OFF |
2 |
bmse_lv_2p |
NIM crate #2, +6V |
OFF |
3 |
bmse_lv_3p |
NIM crate #3, +6V |
OFF |
4 |
bmse_lv_4p |
NIM crate #4, +6V |
OFF |
5 |
bmse_lv_1n |
NIM crate #1, -6V |
OFF |
6 |
bmse_lv_2n |
NIM crate #2, -6V |
OFF |
7 |
bmse_lv_3n |
NIM crate #3, -6V |
OFF |
8 |
bmse_lv_4n |
NIM crate #4, -6V |
OFF |
33 |
mW2_gas_alarm |
Gas alarm from MW2 gas system |
ON |
34 |
mW1_gas_alarm |
Gas alarm from MW1 gas system |
OFF |
35 |
mW1_gas_argon |
Argon gas flow value in MW1 |
OFF |
36 |
mW1_gas_co2 |
CO2 gas flow value in MW1 |
OFF |
37 |
ecal2_hv_signal |
HV system alarm for ECAL2 |
ON |
61 - 62 |
T_W_RET |
Pt4w temp sensor, incoming water for RICH electronics cooling |
ON |
63 - 64 |
T_W_DEP |
Pt4w temp sensor, outgoing water from RICH electronics cooling |
ON |
- ELMB #4
CANbus line #2
ADC mode: unipolar; ADC range: 1 V.
Place: MW1 FE LV power supply rack, SM2 region, Saleve side.
Status: installed.
Comments: In PVSS the factors 0.6, 1.4
and 3.2 in the dp_fct are due to the VME crate itself: 10V means Vout=6V, etc.
ADC channels |
Dp name |
Comments |
Status |
1 |
mW1_C11_5p |
Crate #1, +5V, channel 1 |
ON |
2 |
mW1_C11_5n |
Crate #1, -5V, channel 1 |
ON |
3 |
mW1_C12_5p |
Crate #1, +5V, channel 2 |
ON |
4 |
mW1_C12_5n |
Crate #1, -5V, channel 2 |
ON |
5 |
mW1_C21_5p |
Crate #2, +5V, channel 1 |
ON |
6 |
mW1_C21_5n |
Crate #2, -5V, channel 1 |
ON |
7 |
mW1_C22_5p |
Crate #2, +5V, channel 2 |
ON |
8 |
mW1_C22_5n |
Crate #2, -5V, channel 2 |
ON |
17 |
mW1_V4_5Vp |
Crate VME #4, +5V voltage |
ON |
18 |
mW1_V4_5Ip |
Crate VME #4, +5V current |
ON |
19 |
mW1_V4_12Vp |
Crate VME #4, +12V voltage |
ON |
20 |
mW1_V4_12Ip |
Crate VME #4, +12V current |
ON |
21 |
mW1_V4_12Vn |
Crate VME #4, -12V voltage |
ON |
22 |
mW1_V4_12In |
Crate VME #4, -12V current |
ON |
23 |
mW1_V4_OVT |
Crate VME #4 PS Over-Temperature |
ON |
24 |
mW1_V4_OLD |
Crate VME #4 cards Over-Temperature |
ON |
25 |
mW1_V5_5Vp |
Crate VME #5, +5V voltage |
ON |
26 |
mW1_V5_5Ip |
Crate VME #5, +5V current |
ON |
27 |
mW1_V5_12Vp |
Crate VME #5, +12V voltage |
ON |
28 |
mW1_V5_12Ip |
Crate VME #5, +12V current |
ON |
29 |
mW1_V5_12Vn |
Crate VME #5, -12V voltage |
ON |
30 |
mW1_V5_12In |
Crate VME #5, -12V current |
ON |
31 |
mW1_V5_OVT |
Crate VME #5 PS Over-Temperature |
ON |
32 |
mW1_V5_OLD |
Crate VME #5 cards Over-Temperature |
ON |
63 - 64 |
pt4w_elmb4_T64 |
Pt4w temperature sensor, T5 |
OFF |
- ELMB #5
CANbus line #2
ADC mode: unipolar; ADC range: 100 mV.
Place: SciFiG FE LV power supply rack, SM2 region, Jura side.
Status: installed
ADC channels |
Dp name |
Comments |
Status |
1 |
t1 |
2 wire conn, temp. electronic board |
OFF |
2 |
t2 |
2 wire conn, temp. electronic board |
OFF |
3 |
t3 |
2 wire conn, temp. electronic board |
OFF |
4 |
t4 |
2 wire conn, temp. electronic board |
OFF |
5 |
t5 |
2 wire conn, temp. electronic board |
OFF |
6 |
t6 |
2 wire conn, temp. electronic board |
OFF |
7 |
t7 |
2 wire conn, temp. electronic board |
OFF |
8 |
t8 |
2 wire conn, temp. electronic board |
OFF |
9 |
t9 |
2 wire conn, temp. electronic board |
OFF |
10 |
t10 |
2 wire conn, temp. electronic board |
OFF |
11 |
t11 |
2 wire conn, temp. electronic board |
OFF |
12 |
t12 |
2 wire conn, temp. electronic board |
OFF |
13 |
t13 |
2 wire conn, temp. electronic board |
OFF |
14 |
t14 |
2 wire conn, temp. electronic board |
OFF |
15 |
t15 |
2 wire conn, temp. electronic board |
OFF |
16 |
t16 |
2 wire conn, temp. electronic board |
OFF |
57 |
SM2_M_F |
Hall probe #1 inside magnet SM2 |
OFF |
58 |
SM22_M_F |
Hall probe #2 inside magnet SM2 |
OFF |
63 - 64 |
pt4w_elmb5_T64 |
Temperature inside hall 888, T6 |
ON |
- ELMB #6
CANbus line #2
ADC mode: unipolar; ADC range: 100mV.
Place: STRAW frame, temperature and humidity sensors, Jura side.
Status: installed.
ADC channels |
Dp name |
Comments |
Status |
1 - 2 |
STO3V2_TDS |
Pt4w temperature sensor |
ON |
3 - 4 |
STO3V2_TDM |
Pt4w temperature sensor |
ON |
5 - 6 |
STO3V2_TDJ |
Pt4w temperature sensor |
ON |
7 - 8 |
STO3V2_TMS |
Pt4w temperature sensor |
ON |
9 - 10 |
STO3V2_TMJ |
Pt4w temperature sensor |
ON |
11 - 12 |
STO3V2_TUS |
Pt4w temperature sensor |
ON |
13 - 14 |
STO3V2_TUM |
Pt4w temperature sensor |
ON |
15 - 16 |
STO3V2_TUJ |
Pt4w temperature sensor |
ON |
17 - 18 |
STO3Y2_TDS |
Pt4w temperature sensor |
ON |
19 - 20 |
STO3Y2_TDM |
Pt4w temperature sensor |
ON |
21 - 22 |
STO3Y2_TDJ |
Pt4w temperature sensor |
ON |
23 - 24 |
STO3Y2_TMS |
Pt4w temperature sensor |
ON |
25 - 26 |
STO3Y2_TMJ |
Pt4w temperature sensor |
ON |
27 - 28 |
STO3Y2_TUS |
Pt4w temperature sensor |
ON |
29 - 30 |
STO3Y2_TUM |
Pt4w temperature sensor |
ON |
31 - 32 |
STO3Y2_TUJ |
Pt4w temperature sensor |
ON |
33 - 34 |
STO3X2_TDS |
Pt4w temperature sensor |
ON |
35 - 36 |
STO3X2_TDM |
Pt4w temperature sensor |
ON |
37 - 38 |
STO3X2_TDJ |
Pt4w temperature sensor |
ON |
39 - 40 |
STO3X2_TMS |
Pt4w temperature sensor |
ON |
41 - 42 |
STO3X2_TMJ |
Pt4w temperature sensor |
ON |
43 - 44 |
STO3X2_TUS |
Pt4w temperature sensor |
ON |
45 - 46 |
STO3X2_TUM |
Pt4w temperature sensor |
ON |
47 - 48 |
STO3X2_TUJ |
Pt4w temperature sensor |
ON |
49 |
STO3V2_H |
Humidity sensor |
ON |
50 |
STO3X2_H |
Humidity sensor |
ON |
51 |
STO3Y2_H |
Humidity sensor |
ON |
52 |
STO3X1_H |
Humidity sensor |
ON |
53 |
STO3U1_H |
Humidity sensor |
ON |
54 |
STO3Y1_H |
Humidity sensor |
ON |
- ELMB #7
CANbus line #2
ADC mode: unipolar; ADC range: 100 mV.
Place: RICH rack, temperature sensors inside vessel, Saleve side.
Status: installed.
ADC channels |
Dp name |
Comments |
Status |
1 - 2 |
pt4w-RICH-1 |
Pt4w temperature sensor inside vessel |
OFF |
3 - 4 |
pt4w-RICH-2 |
Pt4w temperature sensor inside vessel |
OFF |
5 - 6 |
pt4w-RICH-3 |
Pt4w temperature sensor inside vessel |
ON |
7 - 8 |
pt4w-RICH-4 |
Pt4w temperature sensor inside vessel |
ON |
9 - 10 |
-pt4w-RICH-5 |
Pt4w temperature sensor inside vessel |
ON |
11 - 12 |
pt4w-RICH-6 |
Pt4w temperature sensor inside vessel |
ON |
13 - 14 |
pt4w-RICH-7 |
Pt4w temperature sensor inside vessel |
ON |
15 - 16 |
pt4w-RICH-8 |
Pt4w temperature sensor inside vessel |
ON |
17 - 18 |
pt4w-RICH-9 |
Pt4w temperature sensor inside vessel |
ON |
19 - 20 |
pt4w-RICH-10 |
Pt4w temperature sensor inside vessel |
ON |
21 - 22 |
pt4w-RICH-11 |
Pt4w temperature sensor inside vessel |
ON |
23 - 24 |
pt4w-RICH-12 |
Pt4w temperature sensor inside vessel |
ON |
25 - 26 |
pt4w-RICH-13 |
Pt4w temperature sensor inside vessel |
ON |
27 - 28 |
pt4w-RICH-14 |
Pt4w temperature sensor inside vessel |
ON |
29 - 30 |
pt4w-RICH-15 |
Pt4w temperature sensor inside vessel |
ON |
31 - 32 |
pt4w-RICH-16 |
Pt4w temperature sensor inside vessel |
ON |
33 - 34 |
pt4w-RICH-17 |
Pt4w temperature sensor inside vessel |
ON |
35 - 36 |
pt4w-RICH-18 |
Pt4w temperature sensor inside vessel |
ON |
37 - 38 |
pt4w-RICH-19 |
Pt4w temperature sensor inside vessel |
OFF |
39 - 40 |
pt4w-RICH-20 |
Pt4w temperature sensor inside vessel |
OFF |
41 - 42 |
pt4w-RICH-21 |
Pt4w temperature sensor inside vessel |
OFF |
43 - 44 |
pt4w-RICH-22 |
Pt4w temperature sensor inside vessel |
OFF |
45 - 46 |
pt4w-RICH-23 |
Pt4w temperature sensor inside vessel |
OFF |
47 - 48 |
pt4w-RICH-24 |
Pt4w temperature sensor inside vessel |
OFF |
49 - 50 |
pt4w-RICH-25 |
Pt4w temperature sensor inside vessel |
OFF |
51 - 52 |
pt4w-RICH-26 |
Pt4w temperature sensor inside vessel |
OFF |
53 - 54 |
pt4w-RICH-27 |
Pt4w temperature sensor inside vessel |
OFF |
55 - 56 |
pt4w-RICH-28 |
Pt4w temperature sensor inside vessel |
OFF |
57 - 58 |
pt4w-RICH-29 |
Pt4w temperature sensor inside vessel |
OFF |
59 - 60 |
pt4w-RICH-30 |
Pt4w temperature sensor inside vessel |
OFF |
61 - 62 |
pt4w-RICH-31 |
Pt4w temperature sensor inside vessel(?) |
ON |
63 - 64 |
pt4w-elmb7-T64 |
Pt4w sensor: temperature inside hall 888, T3 |
ON |
- ELMB #8
CANbus line #2
ADC mode: bipolar; ADC range: 100 mV.
Place: SciFi rack, Saleve side.
Status: installed.
ADC channels |
Dp name |
Comments |
Status |
1 - 2 |
PT_1_HSO |
Pt4w temp sensor, Pol Target horizontal screen outlet |
ON |
3 - 4 |
PT_2_DTF |
Pt4w temp sensor, Pol Target dilution cryostat top flange |
ON |
5 - 6 |
PT_3_SLT |
Pt4w temp sensor, Pol Target still line top |
ON |
7 - 8 |
PT_4_MHG |
Pt4w temp sensor, Pol Target magnet gas outlet |
ON |
9 - 10 |
PT_5_SCW |
Pt4w temp sensor, Pol Target dipole current leads |
ON |
11 - 12 |
PT_6_SFC |
Pt4w temp sensor, Pol Target separator flow control |
ON |
13 - 14 |
PT_7_NMR |
Pt4w temp sensor, Pol Target NMR rack |
ON |
15 - 16 |
PT_8_SCL |
Pt4w temp sensor, Pol Target solenoid current leads |
ON |
17 |
SM1_M_F |
Hall probe for SM1 Magnetic field |
ON |
21 |
Solenoid_Curr |
current for Pol Target Solenoid |
ON |
23 |
Dipole_Curr |
current for Pol Target Dipole magnet |
ON |
31 - 32 |
pt4w-elmb8-T64 |
Pt4w temperature sensor in the hall, T1 |
OFF |
33 - 34 |
SI01_T_u1 |
Pt4w temp sensor, SILICON station 01 |
ON |
35 - 36 |
SI01_T_u2 |
Pt4w temp sensor, SILICON station 01 |
ON |
37 - 38 |
SI01_T_v1 |
Pt4w temp sensor, temporarily on SI02_u1 |
ON |
39 - 40 |
SI01_T_v2 |
Pt4w temp sensor, temporarily on SI02_u2 |
ON |
41 - 42 |
SI01_T_y1 |
Pt4w temp sensor, temporarily on SI02_x1 |
ON |
43 - 44 |
SI01_T_y2 |
Pt4w temp sensor, temporarily on SI02_x2 |
ON |
45 - 46 |
SI01_T_x1 |
Pt4w temp sensor, SILICON station 01 |
ON |
47 - 48 |
SI01_T_x2 |
Pt4w temp sensor, SILICON station 01 |
ON |
49 - 50 |
SI02_T_u1 |
Pt4w temp sensor, temporarily on SI05_u1 |
ON |
51 - 52 |
SI02_T_u2 |
Pt4w temp sensor, temporarily on SI05_u2 |
ON |
53 - 54 |
SI02_T_v1 |
Pt4w temp sensor, temporarily on SI05_v1 |
OFF |
55 - 56 |
SI02_T_v2 |
Pt4w temp sensor, temporarily on SI05_v2 |
OFF |
57 - 58 |
SI02_T_y1 |
Pt4w temp sensor, temporarily on SI05_y1 |
ON |
59 - 60 |
SI02_T_y2 |
Pt4w temp sensor, temporarily on SI05_y2 |
ON |
61 - 62 |
SI02_T_x1 |
Pt4w temp sensor, temporarily on SI05_x1 |
ON |
63 - 64 |
SI02_T_x2 |
Pt4w temp sensor, temporarily on SI05_x2 |
ON |
- ELMB #9
CANbus line #1
ADC mode: unipolar; ADC range: 100 mV.
Place: BMS HV room HNB 202.
Status: installed.
ADC channels |
Dp name |
Comments |
Status |
1 |
bmsh_lv_1 |
Low voltage for amplifier BMS station |
OFF |
2 |
bmsh_lv_2 |
Low voltage for amplifier BMS station |
OFF |
3 |
bmsh_lv_3 |
Low voltage for amplifier BMS station |
OFF |
4 |
bmsh_lv_4 |
Low voltage for amplifier BMS station |
OFF |
5 |
bmsh_lv_5 |
Low voltage for amplifier BMS station |
OFF |
6 |
bmsh_lv_6 |
Low voltage for amplifier BMS station |
OFF |
7 |
bmsh_lv_7 |
Low voltage for amplifier BMS station |
OFF |
8 |
bmsh_lv_8 |
Low voltage for amplifier BMS station |
OFF |
9 |
bmsh_lv_9 |
Low voltage for amplifier BMS station |
OFF |
10 |
bmsh_lv_10 |
Low voltage for amplifier BMS station |
OFF |
11 |
bmsh_lv_11 |
Low voltage for amplifier BMS station |
OFF |
12 |
bmsh_lv_12 |
Low voltage for amplifier BMS station |
OFF |
43 |
B6_M_F |
sensor on Bending Magnet B6 |
ON |
61 - 62 |
AirTemp |
Pt4w sensor, Air temperature outside building 888 |
ON |
63 - 64 |
T_OUT_SIDE |
Pt4w sensor, temperature inside BMS room |
ON |
- ELMB #10
CANbus line #2
ADC mode: unipolar; ADC range: 100 mV.
Place: bld. 888, mMegas/Drifts electronics rack
Status: installed
ADC channels |
Dp name |
Comments |
Status |
1 - 2 |
MM03_UV_1 |
Pt4w temperature sensor for MM |
ON |
3 - 4 |
MM03_UV_2 |
Pt4w temperature sensor for MM |
ON |
5 - 6 |
MM03_UV_3 |
Pt4w temperature sensor for MM |
ON |
7 - 8 |
MM03_UV_4 |
Pt4w temperature sensor for MM |
ON |
9 - 10 |
MM03_XY_1 |
Pt4w temperature sensor for MM |
ON |
11 - 12 |
MM03_XY_2 |
Pt4w temperature sensor for MM |
ON |
13 - 14 |
MM03_XY_3 |
Pt4w temperature sensor for MM |
ON |
15 - 16 |
MM03_XY_4 |
Pt4w temperature sensor for MM |
ON |
17 - 18 |
MM01_UV_1 |
Pt4w temperature sensor for MM |
ON |
19 - 20 |
MM01_UV_2 |
Pt4w temperature sensor for MM |
ON |
21 - 22 |
MM01_UV_3 |
Pt4w temperature sensor for MM |
ON |
23 - 24 |
MM01_UV_4 |
Pt4w temperature sensor for MM |
ON |
25 - 26 |
MM01_XY_1 |
Pt4w temperature sensor for MM |
OFF |
27 - 28 |
MM01_XY_2 |
Pt4w temperature sensor for MM |
OFF |
29 - 30 |
MM01_XY_3 |
Pt4w temperature sensor for MM |
OFF |
31 - 32 |
MM01_XY_4 |
Pt4w temperature sensor for MM |
ON |
33 - 34 |
MM02_XY_1 |
Pt4w temperature sensor for MM |
OFF |
35 - 36 |
MM02_XY_2 |
Pt4w temperature sensor for MM |
OFF |
37 - 38 |
MM02_UV_3 |
Pt4w temperature sensor for MM |
ON |
39 - 40 |
MM02_UV_4 |
Pt4w temperature sensor for MM |
ON |
41 - 42 |
MM02_XY_1 |
Pt4w temperature sensor for MM |
ON |
43 - 44 |
MM02_XY_2 |
Pt4w temperature sensor for MM |
ON |
45 - 46 |
MM02_XY_3 |
Pt4w temperature sensor for MM |
ON |
47 - 48 |
MM02_XY_4 |
Pt4w temperature sensor for MM |
ON |
49 |
DC01_BS_Y2 |
Pt2w temperature sensor for DC |
OFF |
50 |
DC01_TJ_V1 |
Pt2w temperature sensor for DC |
OFF |
51 |
DC01_BS_V2 |
Pt2w temperature sensor for DC |
OFF |
52 |
DC01_TJ_Y1 |
Pt2w temperature sensor for DC |
OFF |
59 |
Hum1_HALL |
Humidity sensor |
ON |
60 |
Patm_hall |
Atmospheric pressure sensor |
ON |
63 - 64 |
pt4w-elmb10-T64 |
Temperature sensor, point T2 |
ON |
- ELMB #11
CANbus line #1
ADC mode: unipolar; ADC range: 100 mV.
Place: bld. 888, MWPC power supply rack
Status: installed
Comments: ELMB #11 and ELMB #12 are mounted
in one box and have common power supply and external wiring for all
CANbus signals.
ADC channels |
Dp name |
Comments |
Status |
1 |
mwpc_8X_6v_vmon |
Low voltage for MWPC station 8 |
ON |
2 |
mwpc_8X_6v_imon |
Low voltage for MWPC station 8 |
ON |
3 |
mwpc_8X_9v_vmon |
Low voltage for MWPC station 8 |
ON |
4 |
mwpc_8X_9v_imon |
Low voltage for MWPC station 8 |
ON |
5 |
mwpc_7X_6v_vmon |
Low voltage for MWPC station 7 |
ON |
6 |
mwpc_7X_6v_imon |
Low voltage for MWPC station 7 |
ON |
7 |
mwpc_7X_9v_vmon |
Low voltage for MWPC station 7 |
ON |
8 |
mwpc_7X_9v_imon |
Low voltage for MWPC station 7 |
ON |
9 |
mwpc_7V_6v_vmon |
Low voltage for MWPC station 7 |
ON |
10 |
mwpc_7V_6v_imon |
Low voltage for MWPC station 7 |
ON |
11 |
mwpc_7V_9v_vmon |
Low voltage for MWPC station 7 |
ON |
12 |
mwpc_7V_9v_imon |
Low voltage for MWPC station 7 |
ON |
13 |
mwpc_7U_6v_vmon |
Low voltage for MWPC station 7 |
ON |
14 |
mwpc_7U_6v_imon |
Low voltage for MWPC station 7 |
ON |
15 |
mwpc_7U_9v_vmon |
Low voltage for MWPC station 7 |
ON |
16 |
mwpc_7U_9v_imon |
Low voltage for MWPC station 7 |
ON |
17 |
mwpc_11U_6v_vmon |
Low voltage for MWPC station 11 |
ON |
18 |
mwpc_11U_6v_imon |
Low voltage for MWPC station 11 |
ON |
19 |
mwpc_11U_9v_vmon |
Low voltage for MWPC station 11 |
ON |
20 |
mwpc_11U_9v_imon |
Low voltage for MWPC station 11 |
ON |
21 |
mwpc_11V_6v_vmon |
Low voltage for MWPC station 11 |
ON |
22 |
mwpc_11V_6v_imon |
Low voltage for MWPC station 11 |
ON |
23 |
mwpc_11V_9v_vmon |
Low voltage for MWPC station 11 |
ON |
24 |
mwpc_11V_9v_imon |
Low voltage for MWPC station 11 |
ON |
25 |
mwpc_11X_6v_vmon |
Low voltage for MWPC station 11 |
ON |
26 |
mwpc_11X_6v_imon |
Low voltage for MWPC station 11 |
ON |
27 |
mwpc_11X_9v_vmon |
Low voltage for MWPC station 11 |
ON |
28 |
mwpc_11X_9v_imon |
Low voltage for MWPC station 11 |
ON |
- ELMB #12
CANbus line #1
ADC mode: unipolar; ADC range: 100 mV.
Place: bld. 888, MWPC power supply rack
Status: installed
Comments: ELMB #11 and ELMB #12 are mounted
in one box and have common power supply and external wiring for all
CANbus signals.
ADC channels |
Dp name |
Comments |
Status |
1 |
mwpc_10V_6v_vmon |
Low voltage for MWPC station 10 |
ON |
2 |
mwpc_10V_6v_imon |
Low voltage for MWPC station 10 |
ON |
3 |
mwpc_10V_9v_vmon |
Low voltage for MWPC station 10 |
ON |
4 |
mwpc_10V_9v_imon |
Low voltage for MWPC station 10 |
ON |
5 |
mwpc_10U_6v_vmon |
Low voltage for MWPC station 10 |
ON |
6 |
mwpc_10U_6v_imon |
Low voltage for MWPC station 10 |
ON |
7 |
mwpc_10U_9v_vmon |
Low voltage for MWPC station 10 |
ON |
8 |
mwpc_10U_9v_imon |
Low voltage for MWPC station 10 |
ON |
9 |
mwpc_10X_6v_vmon |
Low voltage for MWPC station 10 |
ON |
10 |
mwpc_10X_6v_imon |
Low voltage for MWPC station 10 |
ON |
11 |
mwpc_10X_9v_vmon |
Low voltage for MWPC station 10 |
ON |
12 |
mwpc_10X_9v_imon |
Low voltage for MWPC station 10 |
ON |
13 |
mwpc_9X_6v_vmon |
Low voltage for MWPC station 9 |
ON |
14 |
mwpc_9X_6v_imon |
Low voltage for MWPC station 9 |
ON |
15 |
mwpc_9X_9v_vmon |
Low voltage for MWPC station 9 |
ON |
16 |
mwpc_9X_9v_imon |
Low voltage for MWPC station 9 |
ON |
17 |
mwpc_9V_6v_vmon |
Low voltage for MWPC station 9 |
ON |
18 |
mwpc_9V_6v_imon |
Low voltage for MWPC station 9 |
ON |
19 |
mwpc_9V_9v_vmon |
Low voltage for MWPC station 9 |
ON |
20 |
mwpc_9V_9v_imon |
Low voltage for MWPC station 9 |
ON |
21 |
mwpc_9U_6v_vmon |
Low voltage for MWPC station 9 |
ON |
22 |
mwpc_9U_6v_imon |
Low voltage for MWPC station 9 |
ON |
23 |
mwpc_9U_9v_vmon |
Low voltage for MWPC station 9 |
ON |
24 |
mwpc_9U_9v_imon |
Low voltage for MWPC station 9 |
ON |
25 |
mwpc_8V_6v_vmon |
Low voltage for MWPC station 8 |
ON |
26 |
mwpc_8V_6v_imon |
Low voltage for MWPC station 8 |
ON |
27 |
mwpc_8V_9v_vmon |
Low voltage for MWPC station 8 |
ON |
28 |
mwpc_8V_9v_imon |
Low voltage for MWPC station 8 |
ON |
29 |
mwpc_8U_6v_vmon |
Low voltage for MWPC station 8 |
ON |
30 |
mwpc_8U_6v_imon |
Low voltage for MWPC station 8 |
ON |
31 |
mwpc_8U_9v_vmon |
Low voltage for MWPC station 8 |
ON |
32 |
mwpc_8U_9v_imon |
Low voltage for MWPC station 8 |
ON |
63 - 64 |
pt4w_elmb12_T64 |
Temperature inside hall 888, T7 |
OFF |
- ELMB #13
CANbus line #2
ADC mode: unipolar; ADC range: 100 mV.
Place: bld. 888, MWPC power supply rack
Status: installed
Comments: ELMB #13 and ELMB #14 are mounted
in one box and have common power supply and external wiring for all
CANbus signals.
ADC channels |
Dp name |
Comments |
Status |
1 |
mwpc_6X_6v_vmon |
Low voltage for MWPC station 6 |
ON |
2 |
mwpc_6X_6v_imon |
Low voltage for MWPC station 6 |
ON |
3 |
mwpc_6X_9v_vmon |
Low voltage for MWPC station 6 |
ON |
4 |
mwpc_6X_9v_imon |
Low voltage for MWPC station 6 |
ON |
5 |
mwpc_5V_6v_vmon |
Low voltage for MWPC station 5 |
ON |
6 |
mwpc_5V_6v_imon |
Low voltage for MWPC station 5 |
ON |
7 |
mwpc_5V_9v_vmon |
Low voltage for MWPC station 5 |
ON |
8 |
mwpc_5V_9v_imon |
Low voltage for MWPC station 5 |
ON |
9 |
mwpc_2U_6v_vmon |
Low voltage for MWPC station 2 |
ON |
10 |
mwpc_2U_6v_imon |
Low voltage for MWPC station 2 |
ON |
11 |
mwpc_2U_9v_vmon |
Low voltage for MWPC station 2 |
ON |
12 |
mwpc_2U_9v_imon |
Low voltage for MWPC station 2 |
ON |
13 |
mwpc_2V_6v_vmon |
Low voltage for MWPC station 2 |
ON |
14 |
mwpc_2V_6v_imon |
Low voltage for MWPC station 2 |
ON |
15 |
mwpc_2V_9v_vmon |
Low voltage for MWPC station 2 |
ON |
16 |
mwpc_2V_9v_imon |
Low voltage for MWPC station 2 |
ON |
17 |
mwpc_2X_6v_vmon |
Low voltage for MWPC station 2 |
ON |
18 |
mwpc_2X_6v_imon |
Low voltage for MWPC station 2 |
ON |
19 |
mwpc_2X_9v_vmon |
Low voltage for MWPC station 2 |
ON |
20 |
mwpc_2X_9v_imon |
Low voltage for MWPC station 2 |
ON |
21 |
mwpc_3X_6v_vmon |
Low voltage for MWPC station 3 |
ON |
22 |
mwpc_3X_6v_imon |
Low voltage for MWPC station 3 |
ON |
23 |
mwpc_3X_9v_vmon |
Low voltage for MWPC station 3 |
ON |
24 |
mwpc_3X_9v_imon |
Low voltage for MWPC station 3 |
ON |
25 |
mwpc_3U_6v_vmon |
Low voltage for MWPC station 3 |
ON |
26 |
mwpc_3U_6v_imon |
Low voltage for MWPC station 3 |
ON |
27 |
mwpc_3U_9v_vmon |
Low voltage for MWPC station 3 |
ON |
28 |
mwpc_3U_9v_imon |
Low voltage for MWPC station 3 |
ON |
29 |
mwpc_3V_6v_vmon |
Low voltage for MWPC station 3 |
ON |
30 |
mwpc_3V_6v_imon |
Low voltage for MWPC station 3 |
ON |
31 |
mwpc_3V_9v_vmon |
Low voltage for MWPC station 3 |
ON |
32 |
mwpc_3V_9v_imon |
Low voltage for MWPC station 3 |
ON |
63 - 64 |
pt4w_elmb13_T64 |
Pt4w temperature sensor |
OFF |
- ELMB #14
CANbus line #2
ADC mode: unipolar; ADC range: 100 mV.
Place: bld. 888, MWPC power supply rack
Status: installed.
Comments: ELMB #13 and ELMB #14 are mounted
in one box and have common power supply and external wiring for all
CANbus signals.
ADC channels |
Dp name |
Comments |
Status |
1 |
mwpc_4U_6v_vmon |
Low voltage for MWPC station 4 |
ON |
2 |
mwpc_4U_6v_imon |
Low voltage for MWPC station 4 |
ON |
3 |
mwpc_4U_9v_vmon |
Low voltage for MWPC station 4 |
ON |
4 |
mwpc_4U_9v_imon |
Low voltage for MWPC station 4 |
ON |
5 |
mwpc_4V_6v_vmon |
Low voltage for MWPC station 4 |
ON |
6 |
mwpc_4V_6v_imon |
Low voltage for MWPC station 4 |
ON |
7 |
mwpc_4V_9v_vmon |
Low voltage for MWPC station 4 |
ON |
8 |
mwpc_4V_9v_imon |
Low voltage for MWPC station 4 |
ON |
9 |
mwpc_4X_6v_vmon |
Low voltage for MWPC station 4 |
ON |
10 |
mwpc_4X_6v_imon |
Low voltage for MWPC station 4 |
ON |
11 |
mwpc_4X_9v_vmon |
Low voltage for MWPC station 4 |
ON |
12 |
mwpc_4X_9v_imon |
Low voltage for MWPC station 4 |
ON |
13 |
mwpc_5X_6v_vmon |
Low voltage for MWPC station 5 |
ON |
14 |
mwpc_5X_6v_imon |
Low voltage for MWPC station 5 |
ON |
15 |
mwpc_5X_9v_vmon |
Low voltage for MWPC station 5 |
ON |
16 |
mwpc_5X_9v_imon |
Low voltage for MWPC station 5 |
ON |
17 |
mwpc_5U_6v_vmon |
Low voltage for MWPC station 5 |
ON |
18 |
mwpc_5U_6v_imon |
Low voltage for MWPC station 5 |
ON |
19 |
mwpc_5U_9v_vmon |
Low voltage for MWPC station 5 |
ON |
20 |
mwpc_5U_9v_imon |
Low voltage for MWPC station 5 |
ON |
25 |
mwpc_6V_6v_vmon |
Low voltage for MWPC station 6 |
ON |
26 |
mwpc_6V_6v_imon |
Low voltage for MWPC station 6 |
ON |
27 |
mwpc_6V_9v_vmon |
Low voltage for MWPC station 6 |
ON |
28 |
mwpc_6V_9v_imon |
Low voltage for MWPC station 6 |
ON |
29 |
mwpc_6U_6v_vmon |
Low voltage for MWPC station 6 |
ON |
30 |
mwpc_6U_6v_imon |
Low voltage for MWPC station 6 |
ON |
31 |
mwpc_6U_9v_vmon |
Low voltage for MWPC station 6 |
ON |
32 |
mwpc_6U_9v_imon |
Low voltage for MWPC station 6 |
ON |
63 - 64 |
pt4w_elmb14_T64 |
Pt4w temperature sensor inside hall 888, T8 |
ON |
- ELMB #15
CANbus line #2
ADC mode:unipolar; ADC range: 100 mV.
Place: bld. 888, on gallery, Jura side
Status: installed.
ADC channels |
Dp name |
Comments |
Status |
1 |
mwpc_1X_6v_vmon |
Low voltage for MWPC station 1 |
ON |
2 |
mwpc_1X_6v_imon |
Low voltage for MWPC station 1 |
ON |
3 |
mwpc_1X_9v_vmon |
Low voltage for MWPC station 1 |
ON |
4 |
mwpc_1X_9v_imon |
Low voltage for MWPC station 1 |
ON |
5 |
mwpc_1Y_6v_vmon |
Low voltage for MWPC station 1 |
ON |
6 |
mwpc_1Y_6v_imon |
Low voltage for MWPC station 1 |
ON |
7 |
mwpc_1Y_9v_vmon |
Low voltage for MWPC station 1 |
ON |
8 |
mwpc_1Y_9v_imon |
Low voltage for MWPC station 1 |
ON |
9 |
mwpc_1V_6v_vmon |
Low voltage for MWPC station 1 |
ON |
10 |
mwpc_1V_6v_imon |
Low voltage for MWPC station 1 |
ON |
11 |
mwpc_1V_9v_vmon |
Low voltage for MWPC station 1 |
ON |
12 |
mwpc_1V_9v_imon |
Low voltage for MWPC station 1 |
ON |
13 |
mwpc_1U_6v_vmon |
Low voltage for MWPC station 1 |
ON |
14 |
mwpc_1U_6v_imon |
Low voltage for MWPC station 1 |
ON |
15 |
mwpc_1U_9v_vmon |
Low voltage for MWPC station 1 |
ON |
16 |
mwpc_1U_9v_imon |
Low voltage for MWPC station 1 |
ON |
63 - 64 |
pt4w-elmb15-T64 |
Pt4w temperature sensor inside hall 888, T10 |
ON |
- ELMB #16
CANbus line #1
ADC mode: bipolar; ADC range: 1 V.
Place: Trigger room HNB422
Status: installed.
Comments: Automated system for Gas distribution in the area
provides 3 switches. A small current is injected to give the signal (closed=on=alarm). Also
PS for Veto Box gives current and voltage (scaling factors applied in PVSS according to the PS info
-> 1V=0.4A and 1V=3.33 KV).
ADC channels |
Dp name |
Comments |
Status |
1 - 2 |
Temp_NIM_1 |
Pt4w temperature sensor, inside ELMB box |
ON |
58 |
VBX_PS_V |
Voltage from Veto Box PS unit |
ON |
59 |
VBX_PS_I |
Current from Veto Box PS unit |
ON |
62 |
Gas_lv3_alarm |
Level 3 alarm from Gas gen. distrib. system |
ON |
63 |
Gas_gen_alarm |
General alarm from Gas gen. distrib. system |
ON |
64 |
Gas_lv2_alarm |
Level 2 alarm from Gas gen. distrib. system |
ON |
- ELMB #17
CANbus line #2
ADC mode: unipolar; ADC range: 100 mV.
Place: bld. 888, STRAW frame, close to ELMB #6 (?)
Status: installed (?)
- ELMB #18
CANbus line #1
ADC mode: bipolar; ADC range: 1 V.
Place: Trigger room HNB429
Status: installed, but NOT connected to sensors, NO Data Points in PVSS (?).
- ELMB #19
CANbus line #1
ADC mode: unipolar; ADC range 100 mV.
Place: bld. 888, beam area downstream, MW2 power supply rack.
Status: installed.
ADC channels |
Dp name |
Comments |
Status |
1 |
LAX1_N1 |
Amplifier for X1, mW2 low voltage PS |
ON |
2 |
LAX1_N2 |
Amplifier for X1, mW2 low voltage PS |
ON |
3 |
LAX1_P |
Amplifier for V1, mW2 low voltage PS |
ON |
4 |
LTX1_P |
Amplifier for V1, mW2 low voltage PS |
ON |
5 |
LAY1_N1 |
Amplifier for X2, mW2 low voltage PS |
ON |
6 |
LAY1_P |
Amplifier for X2, mW2 low voltage PS |
ON |
7 |
LTY1_P |
Amplifier for V2, mW2 low voltage PS |
ON |
8 |
LAU1_N1 |
Amplifier for V2, mW2 low voltage PS |
ON |
9 |
LAU1_N2 |
Not used |
OFF |
10 |
LAU1_P |
Amplifier for Y1, mW2 low voltage PS |
ON |
11 |
LTU1_P |
Not used |
OFF |
12 |
LAX2_N1 |
Amplifier for Y2, mW2 low voltage PS |
ON |
13 |
LAX2_N2 |
TDC for X,V, mW2 low voltage PS |
ON |
14 |
LAX2_P |
Thresholds Y1,Y2, mW2 low voltage PS |
ON |
15 |
LTX2_P |
TDC for Y, mW2 low voltage PS |
ON |
16 |
LAY2_N1 |
Not used |
OFF |
17 |
LAY2_P |
Thresholds X1,V1, mW2 low voltage PS |
ON |
18 |
LTY2_P |
Thresholds X2,V2, mW2 low voltage PS |
ON |
19 |
LAU2_N1 |
Not used |
OFF |
20 |
LAU2_N2 |
Not used |
OFF |
21 |
LAU2_P |
Not used |
OFF |
22 |
LTU2_P |
Not used |
OFF |
63 - 64 |
pt4w_elmb19_T64 |
Pt4w temperature sensor, T7 |
ON |
- ELMB #20
CANbus line #1
ADC mode: unipolar; ADC range: 100 mV.
Place: bld. 888, W45 power supply rack.
Status: installed.
ADC channels |
Dp name |
Comments |
Status |
1 |
W5_1_6V |
voltage, low voltage PS for W45 |
ON |
2 |
W5_1_6A |
current, low voltage PS for W45 |
ON |
3 |
W5_1_9V |
voltage, low voltage PS for W45 |
ON |
4 |
W5_1_9A |
current, low voltage PS for W45 |
ON |
5 |
W5_2_6V |
voltage, low voltage PS for W45 |
ON |
6 |
W5_2_6A |
current, low voltage PS for W45 |
ON |
7 |
W5_2_9V |
voltage, low voltage PS for W45 |
ON |
8 |
W5_2_9A |
current, low voltage PS for W45 |
ON |
9 |
W4_1_6V |
voltage, low voltage PS for W45 |
ON |
10 |
W4_1_6A |
current, low voltage PS for W45 |
ON |
11 |
W4_1_9V |
voltage, low voltage PS for W45 |
ON |
12 |
W4_1_9A |
current, low voltage PS for W45 |
ON |
13 |
W4_2_6V |
voltage, low voltage PS for W45 |
ON |
14 |
W4_2_6A |
current, low voltage PS for W45 |
ON |
15 |
W4_2_9V |
voltage, low voltage PS for W45 |
ON |
16 |
W4_2_9A |
current, low voltage PS for W45 |
ON |
17 |
W2_1_6V |
voltage, low voltage PS for W45 |
ON |
18 |
W2_1_6A |
current, low voltage PS for W45 |
ON |
19 |
W2_1_9V |
voltage, low voltage PS for W45 |
ON |
20 |
W2_1_9A |
current, low voltage PS for W45 |
ON |
21 |
W2_2_6V |
voltage, low voltage PS for W45 |
ON |
22 |
W2_2_6A |
current, low voltage PS for W45 |
ON |
23 |
W2_2_9V |
voltage, low voltage PS for W45 |
ON |
24 |
W2_2_9A |
current, low voltage PS for W45 |
ON |
25 |
W1_1_6V |
voltage, low voltage PS for W45 |
ON |
26 |
W1_1_6A |
current, low voltage PS for W45 |
ON |
27 |
W1_1_9V |
voltage, low voltage PS for W45 |
ON |
28 |
W1_1_9A |
current, low voltage PS for W45 |
ON |
29 |
W1_2_6V |
voltage, low voltage PS for W45 |
ON |
30 |
W1_2_6A |
current, low voltage PS for W45 |
ON |
31 |
W1_2_9V |
voltage, low voltage PS for W45 |
ON |
32 |
W1_2_9A |
current, low voltage PS for W45 |
ON |
33 - 34 |
DW05_jura |
Pt4w temperature sensor on W45 |
OFF |
35 - 36 |
DW05_bottom |
Pt4w temperature sensor on W45 |
OFF |
37 - 38 |
DW05_saleve |
Pt4w temperature sensor on W45 |
OFF |
39 - 40 |
DW05_electr |
Pt4w temperature sensor on W45 |
OFF |
41 - 42 |
DW06_jura |
Pt4w temperature sensor on W45 |
OFF |
43 - 44 |
DW06_bottom |
Pt4w temperature sensor on W45 |
OFF |
45 - 46 |
DW06_saleve |
Pt4w temperature sensor on W45 |
OFF |
47 - 48 |
DW06_electr |
Pt4w temperature sensor on W45 |
OFF |
- ELMB #21
CANbus line #2
ADC mode: unipolar; ADC range: 100 mV.
Place: bld. 888, Straw station 5 frame.
Status: installed.
ADC channels |
Dp name |
Comments |
Status |
1 - 2 |
ST05X1_TDS |
Pt4w temp sensor, Straw station 5 |
ON |
3 - 4 |
ST05X1_TDM |
Pt4w temp sensor, Straw station 5 |
ON |
5 - 6 |
ST05X1_TDJ |
Pt4w temp sensor, Straw station 5 |
ON |
7 - 8 |
ST05X1_TMS |
Pt4w temp sensor, Straw station 5 |
ON |
9 - 10 |
ST05X1_TMJ |
Pt4w temp sensor, Straw station 5 |
ON |
11 - 12 |
ST05X1_TUS |
Pt4w temp sensor, Straw station 5 |
ON |
13 - 14 |
ST05X1_TUM |
Pt4w temp sensor, Straw station 5 |
ON |
15 - 16 |
ST05X1_TUJ |
Pt4w temp sensor, Straw station 5 |
ON |
17 - 18 |
ST05Y1_TDS |
Pt4w temp sensor, Straw station 5 |
ON |
19 - 20 |
ST05Y1_TDM |
Pt4w temp sensor, Straw station 5 |
ON |
21 - 22 |
ST05Y1_TDJ |
Pt4w temp sensor, Straw station 5 |
ON |
23 - 24 |
ST05Y1_TMS |
Pt4w temp sensor, Straw station 5 |
ON |
25 - 26 |
ST05Y1_TMJ |
Pt4w temp sensor, Straw station 5 |
ON |
27 - 28 |
ST05Y1_TUS |
Pt4w temp sensor, Straw station 5 |
ON |
29 - 30 |
ST05Y1_TUM |
Pt4w temp sensor, Straw station 5 |
ON |
31 - 32 |
ST05Y1_TUJ |
Pt4w temp sensor, Straw station 5 |
ON |
33 - 34 |
ST05U1_TDS |
Pt4w temp sensor, Straw station 5 |
ON |
35 - 36 |
ST05U1_TDM |
Pt4w temp sensor, Straw station 5 |
ON |
37 - 38 |
ST05U1_TDJ |
Pt4w temp sensor, Straw station 5 |
ON |
39 - 40 |
ST05U1_TMS |
Pt4w temp sensor, Straw station 5 |
ON |
41 - 42 |
ST05U1_TMJ |
Pt4w temp sensor, Straw station 5 |
ON |
43 - 44 |
ST05U1_TUS |
Pt4w temp sensor, Straw station 5 |
ON |
45 - 46 |
ST05U1_TUM |
Pt4w temp sensor, Straw station 5 |
ON |
47 - 48 |
ST05U1_TUJ |
Pt4w temp sensor, Straw station 5 |
ON |
49 |
ST05X1_H |
Humidity sensor, Straw station 5 |
ON |
50 |
ST05Y1_H |
Humidity sensor, Straw station 5 |
ON |
51 |
ST05U1_H |
Humidity sensor, Straw station 5 |
ON |
- ELMB #22
CANbus line #2
ADC mode: unipolar; ADC range: 100 mV.
Place: bld. 888, Straw station 6 frame.
Status: installed.
ADC channels |
Dp name |
Comments |
Status |
1 - 2 |
ST06V1_TDS |
Pt4w temp sensor, Straw station 6 |
ON |
3 - 4 |
ST06V1_TDM |
Pt4w temp sensor, Straw station 6 |
OFF |
5 - 6 |
ST06V1_TDJ |
Pt4w temp sensor, Straw station 6 |
ON |
7 - 8 |
ST06V1_TMS |
Pt4w temp sensor, Straw station 6 |
ON |
9 - 10 |
ST06V1_TMJ |
Pt4w temp sensor, Straw station 6 |
ON |
11 - 12 |
ST06V1_TUS |
Pt4w temp sensor, Straw station 6 |
ON |
13 - 14 |
ST06V1_TUM |
Pt4w temp sensor, Straw station 6 |
ON |
15 - 16 |
ST06V1_TUJ |
Pt4w temp sensor, Straw station 6 |
ON |
17 - 18 |
ST06Y1_TDS |
Pt4w temp sensor, Straw station 6 |
ON |
19 - 20 |
ST06Y1_TDM |
Pt4w temp sensor, Straw station 6 |
ON |
21 - 22 |
ST06Y1_TDJ |
Pt4w temp sensor, Straw station 6 |
ON |
23 - 24 |
ST06Y1_TMS |
Pt4w temp sensor, Straw station 6 |
ON |
25 - 26 |
ST06Y1_TMJ |
Pt4w temp sensor, Straw station 6 |
ON |
27 - 28 |
ST06Y1_TUS |
Pt4w temp sensor, Straw station 6 |
ON |
29 - 30 |
ST06Y1_TUM |
Pt4w temp sensor, Straw station 6 |
ON |
31 - 32 |
ST06Y1_TUJ |
Pt4w temp sensor, Straw station 6 |
ON |
33 - 34 |
ST06X1_TDS |
Pt4w temp sensor, Straw station 6 |
ON |
35 - 36 |
ST06X1_TDM |
Pt4w temp sensor, Straw station 6 |
ON |
37 - 38 |
ST06X1_TDJ |
Pt4w temp sensor, Straw station 6 |
ON |
39 - 40 |
ST06X1_TMS |
Pt4w temp sensor, Straw station 6 |
ON |
41 - 42 |
ST06X1_TMJ |
Pt4w temp sensor, Straw station 6 |
ON |
43 - 44 |
ST06X1_TUS |
Pt4w temp sensor, Straw station 6 |
ON |
45 - 46 |
ST06X1_TUM |
Pt4w temp sensor, Straw station 6 |
ON |
47 - 48 |
ST06X1_TUJ |
Pt4w temp sensor, Straw station 6 |
ON |
49 |
ST06V1_H |
Humidity sensor, Straw station 6 |
ON |
50 |
ST06Y1_H |
Humidity sensor, Straw station 6 |
ON |
51 |
ST06X1_H |
Humidity sensor, Straw station 6 |
OFF |
- ELMB #23
CANbus line #1
ADC mode: unipolar; ADC range: 100 mV.
Place: bld. 888, (?).
Status: installed.
ADC channels |
Dp name |
Comments |
Status |
1 - 2 |
DW01_UP |
Pt4w temperature sensor |
OFF |
3 - 4 |
DW01_DOWN |
Pt4w temperature sensor |
ON |
5 - 6 |
DW01_RIGHT |
Pt4w temperature sensor |
ON |
7 - 8 |
DW01_LEFT |
Pt4w temperature sensor |
ON |
9 - 10 |
DW02_UP |
Pt4w temperature sensor |
ON |
11 - 12 |
DW02_DOWN |
Pt4w temperature sensor |
ON |
13 - 14 |
DW02_LEFT |
Pt4w temperature sensor |
ON |
15 - 16 |
DW02_RIGHT |
Pt4w temperature sensor |
ON |
17 - 18 |
DW03_UP |
Pt4w temperature sensor |
ON |
19 - 20 |
DW03_DOWN |
Pt4w temperature sensor |
ON |
21 - 22 |
DW03_LEFT |
Pt4w temperature sensor |
ON |
23 - 24 |
DW03_RIGHT |
Pt4w temperature sensor |
ON |
25 - 26 |
DW04_UP |
Pt4w temperature sensor |
ON |
27 - 28 |
DW04_DOWN |
Pt4w temperature sensor |
ON |
29 - 30 |
DW04_LEFT |
Pt4w temperature sensor |
ON |
31 - 32 |
DW04_RIGHT |
Pt4w temperature sensor |
OFF |
33 - 34 |
DW05_UP |
Pt4w temperature sensor |
OFF |
35 - 36 |
DW05_DOWN |
Pt4w temperature sensor |
ON |
37 - 38 |
DW05_LEFT |
Pt4w temperature sensor |
ON |
39 - 40 |
DW05_RIGHT |
Pt4w temperature sensor |
ON |
41 - 42 |
DW06_UP |
Pt4w temperature sensor |
ON |
43 - 44 |
DW06_DOWN |
Pt4w temperature sensor |
ON |
45 - 46 |
DW06_LEFT |
Pt4w temperature sensor |
ON |
47 - 48 |
DW06_RIGHT |
Pt4w temperature sensor |
ON |
- ELMB #24
CANbus line #2
ADC mode: unipolar; ADC range: 100 mV.
Place: bld. 888, (?).
Status: installed.
ADC channels |
Dp name |
Comments |
Status |
3 - 4 |
DC02_TS_U3 |
Pt4w temperature sensor |
ON |
5 - 6 |
DC02_2 |
Pt4w temperature sensor |
OFF |
7 - 8 |
DC02_BS_X1 |
Pt4w temperature sensor |
ON |
9 - 10 |
DC02_4 |
Pt4w temperature sensor |
OFF |
17 |
DC03_2 |
Pt2w temperature sensor |
OFF |
18 |
DC03_1 |
Pt2w temperature sensor |
OFF |
19 |
DC03_3 |
Pt2w temperature sensor |
OFF |
- ELMB #25
CANbus line #2
ADC mode: unipolar; ADC range: 100 mV.
Place: bld. 888, (?).
Status: installed.
ADC channels |
Dp name |
Comments |
Status |
1 - 2 |
pt4w_RICH_32 |
Pt4w temperature sensor |
OFF |
3 - 4 |
pt4w_RICH_33 |
Pt4w temperature sensor |
OFF |
5 - 6 |
pt4w_RICH_34 |
Pt4w temperature sensor |
OFF |
7 - 8 |
pt4w_RICH_35 |
Pt4w temperature sensor |
OFF |
9 - 10 |
pt4w-RICH-36 |
Pt4w temperature sensor |
OFF |
11 - 12 |
pt4w-RICH-37 |
Pt4w temperature sensor |
OFF |
13 - 14 |
pt4w-RICH-38 |
Pt4w temperature sensor |
OFF |
15 - 16 |
pt4w-RICH-39 |
Pt4w temperature sensor |
OFF |
17 - 18 |
pt4w-RICH-40 |
Pt4w temperature sensor |
OFF |
19 - 20 |
pt4w-RICH-41 |
Pt4w temperature sensor |
OFF |
21 - 22 |
pt4w-RICH-42 |
Pt4w temperature sensor |
OFF |
23 - 24 |
pt4w-RICH-43 |
Pt4w temperature sensor |
OFF |
25 - 26 |
pt4w-RICH-44 |
Pt4w temperature sensor |
OFF |
27 - 28 |
pt4w-RICH-45 |
Pt4w temperature sensor |
OFF |
29 - 30 |
pt4w-RICH-46 |
Pt4w temperature sensor |
OFF |
31 - 32 |
pt4w-RICH-47 |
Pt4w temperature sensor |
OFF |
33- 34 |
pt4w-RICH-48 |
Pt4w temperature sensor |
OFF |
35- 36 |
pt4w-RICH-49 |
Pt4w temperature sensor |
OFF |
37- 38 |
pt4w-RICH-50 |
Pt4w temperature sensor |
OFF |
39 - 40 |
pt4w-RICH-51 |
Pt4w temperature sensor |
OFF |
41 - 42 |
pt4w-RICH-52 |
Pt4w temperature sensor |
OFF |
- ELMB #26
CANbus line #3
ADC mode: unipolar; ADC range: 100 mV.
Place: bld. 888, beam area, small silicon rack under target platform.
Comments: ELMB installed inside ELMB box
belonging to Silicon group.
Status: installed.
ADC channels |
Dp name |
Comments |
Status |
1 |
SI03_T_u1 |
Pt4w temperature sensor |
ON |
2 |
SI03_T_v1 |
Pt4w temperature sensor |
ON |
3 |
SI03_T_v2 |
Pt4w temperature sensor |
ON |
4 |
SI03_T_x1 |
Pt4w temperature sensor |
ON |
5 |
SI03_T_y1 |
Pt4w temperature sensor |
ON |
6 |
SI03_T_y2 |
Pt4w temperature sensor |
ON |
- ELMB #27
CANbus line #3
ADC mode: unipolar; ADC range: 100 mV.
Place: bld. 888, beam area, small silicon rack under target platform.
Comments: ELMB installed inside ELMB box
belonging to Silicon group.
Status: installed.
ADC channels |
Dp name |
Comments |
Status |
1 |
SI04_T_u1 |
Pt4w temperature sensor |
ON |
2 |
SI04_T_v1 |
Pt4w temperature sensor |
ON |
3 |
SI04_T_v2 |
Pt4w temperature sensor |
ON |
4 |
SI04_T_x1 |
Pt4w temperature sensor |
ON |
5 |
SI04_T_y1 |
Pt4w temperature sensor |
ON |
6 |
SI04_T_y2 |
Pt4w temperature sensor |
ON |
- ELMB #28
CANbus line #3
ADC mode: unipolar; ADC range: 100 mV.
Place: bld. 888, beam area, small silicon rack under target platform.
Comments: ELMB installed inside ELMB box
belonging to Silicon group.
Status: installed.
ADC channels |
Dp name |
Comments |
Status |
1 |
SI05_T_u1 |
Pt4w temperature sensor |
ON |
2 |
SI05_T_v1 |
Pt4w temperature sensor |
ON |
3 |
SI05_T_v2 |
Pt4w temperature sensor |
ON |
4 |
SI05_T_x1 |
Pt4w temperature sensor |
ON |
5 |
SI05_T_y1 |
Pt4w temperature sensor |
ON |
6 |
SI05_T_y2 |
Pt4w temperature sensor |
ON |
Last update: 13 October 2004