COMPASS

Flammable Gas Detection System


Positions of the Detection Heads


serial
number 1)
red label
number
calibrated2)
for
alarm level
2 / 3
[% LEL3)]
date of
last
calibration
position
Bld. 908, gas cylinder storage
729 00 Methane 15 / 30 -4) upper ventilation,
above CF4 supply racks
730 01 Isobutane 15 / 30 -4) lower ventilation,
above Neon supply
731 02 Methane 15 / 30 -4) upper ventilation,
above empty supply
732 03 Isobutane 15 / 30 -4) bottom ventilation,
above Isobutane supply
733 04 Methane 15 / 30 -4) upper ventilation,
above Methane supply
Bld. 888, gas mixing zone
735 08 Isobutane 10 / 20 April 2002 primary supply rack,
bottom
737 10 Isobutane 10 / 20 April 2002 DC / MicroMega supply,
bottom
785 30 Methane 5 / 10 April 2002 ventilation hood no.1
(RICH CsI, MW2)
784 29 Methane 5 / 10 April 2002 ventilation hood no.2
(primary supply rack, top)
783 28 Methane 5 / 10 April 2002 ventilation hood no.3
(MW1)
782 27 Ethane 5 / 10 April 2002 ventilation hood no.4
(DC, MicroM)
Bld. 888, RICH test area
- - (Methane) 10 / 20 April 2002 sensor dismounted
Bld. 888, experimental hall
739 14 Isobutane 10 / 20 April 2002 MicroMega and DC,
below PT platform
(upstream of SM1)
740 15 Methane 10 / 20 April 2002 at RICH CSI, bottom, Jura side
742 17 Methane 10 / 20 April 2002 at RICH CSI, top, Jura side
741 - Isobutane 10 / 20 April 2002 MW2
842 (?) - Methane 10 / 20 May 2002 MW2
736 - Methane 10 / 20 May 2002 MW2
? 20 Ethane ? - sampling system: DC2 & DC3
(downstream SM1), top, Jura side 5)
738 11 Methane 10 / 20 April 2002 sampling system: DC3, (downstream
of SM1), on the floor, Jura side 5)

1): serial numbers are of the type: CDGA-00xxx
2): the heads are most sensitive for this type of gas, but can also detect the other types of flammable gases which are used at COMPASS (higher concentration of the gas is needed, so it takes longer until the alarm is triggered)
3): Lower Explosive Level (The ignition ranges in the air are for Methane: 4.4% ... 16.4%, for Ethane: 2.7% ... 14.7% and for Isobutane: 1.3% ... 8.5%)
4): not under the responsibility of NA58
5): only intake nozzle, the sensor itself is located outside the experimental area, near the alarm panel


This page was last updated on April 24, 2003 by Christoph Ilgner